This free journeyman electrician study guide walks through the core knowledge the licensing exam tests, organized around the National Electrical Code (NEC, NFPA 70) that the exam is built on.[1]
It’s interactive, not a wall of text: every module has built-in checkpoint quizzes, flashcards, and practice questions, so you learn by doing — not just reading.
The journeyman exam is state-administered (often delivered by PSI or Prometric) and varies by jurisdiction, but it always rests on three pillars: electrical theory, electrical calculations, and NEC code lookup. We teach them in five study modules.
Read a module, test yourself at each checkpoint, then drill gaps with our free practice test and flashcards. This guide is a high-yield overview that maps the tested content — not a replacement for the Code book itself.
Journeyman Electrician Exam Snapshot
| Detail | Journeyman Electrician Exam |
|---|---|
| Questions | ≈80–100 multiple choice (e.g., Texas: 80) |
| Format | Multiple choice, computer-based; usually open-book (NEC) |
| Time | ≈4 hours (e.g., Texas: 240 minutes) |
| Passing score | ≈70% correct (set by each jurisdiction) |
| Code basis | National Electrical Code, NFPA 70 (current: 2023; many states on 2020/2017) |
| Delivery | State licensing board, commonly via PSI or Prometric |
| Certifying body | State electrical board / licensing agency |
| Recertification | Periodic license renewal + continuing education (varies by state) |
Because the exam is largely code-based and open-book, two skills decide your score: doing the standard calculations quickly, and navigating the NEC to the right article and table fast.[1] Plan your study by where the questions cluster:
Topic proportions are approximate and based on common state journeyman content outlines (for example, the Texas TDLR/PSI outline); exact weights differ by jurisdiction and Code cycle.[6]
Module 1 · Electrical Theory & Calculations
The math under everything else. You can’t size conductors, set overcurrent protection, or check a service without the theory behind it. This module covers Ohm’s law and power, series and parallel circuits, and voltage drop.
1.1 Ohm’s Law & Power
Everything starts with : E = I × R, where voltage (E) equals current (I) times resistance (R). Rearranged, I = E ÷ R and R = E ÷ I. Power in watts is P = E × I, and with Ohm’s law also P = I² × R or P = E² ÷ R.[8]
| To find… | Use | …or |
|---|---|---|
| Voltage (E, volts) | E = I × R | E = P ÷ I |
| Current (I, amperes) | I = E ÷ R | I = P ÷ E |
| Resistance (R, ohms) | R = E ÷ I | R = E² ÷ P |
| Power (P, watts) | P = E × I | P = I² × R |
AC adds two wrinkles the exam loves. For power, multiply by : P = E × I × PF. For , also multiply by the square root of three: P = 1.732 × E × I × PF. Memorize that 1.732 — it shows up on nearly every three-phase question.
| Quantity | Symbol | Unit | Key formula |
|---|---|---|---|
| Voltage | E (or V) | Volt (V) | E = I × R |
| Current | I | Ampere (A) | I = E ÷ R |
| Resistance | R | Ohm (Ω) | R = E ÷ I |
| Power | P | Watt (W) | P = E × I |
1.2 Series & Parallel Circuits
In a there is one path: the current is the same everywhere, and resistances add (R = R₁ + R₂ + R₃). Open it anywhere and everything goes dark. In a there are multiple paths: the voltage is the same across every branch, and the total resistance is less than the smallest branch.
Series circuit
One path. Open it anywhere and everything goes dark.
- Current is the same through every component
- Resistances add: R = R₁ + R₂ + R₃
- Voltage divides across the resistors
Parallel circuit
Multiple paths. One branch can open and the rest stay on — the way building circuits are wired.
- Voltage is the same across every branch
- 1/R = 1/R₁ + 1/R₂ + 1/R₃
- Two equal resistors in parallel = half the value
For parallel resistances, 1/R = 1/R₁ + 1/R₂ + 1/R₃. A handy shortcut: two equal resistors in parallel give exactly half the value (two 20-ohm resistors in parallel = 10 ohms). Building branch circuits are wired in parallel so each device gets full voltage and one failure doesn’t kill the rest.
| Property | Series | Parallel |
|---|---|---|
| Current | Same through every component | Divides among the branches |
| Voltage | Divides across the resistors | Same across every branch |
| Total resistance | Adds: R = R₁ + R₂ + … | 1/R = 1/R₁ + 1/R₂ + … (less than smallest) |
| If one opens | Whole circuit stops | Only that branch stops |
1.3 Voltage Drop
is the voltage lost to a conductor’s resistance as current flows. It grows with longer runs, smaller wire, and more current. The NEC recommends keeping drop to 3% on a branch circuit or feeder and 5% total so motors and equipment run properly.[1]
The single-phase formula is VD = (2 × K × I × L) ÷ CM, where K ≈ 12.9 for copper (21.2 for aluminum), I is the current, L is the one-way length in feet, and CM is the conductor’s circular mils. For three-phase, replace the 2 with 1.732. Excess drop dims lights, slows motors, and wastes energy as heat.
| Change | Effect on voltage drop |
|---|---|
| Longer conductor run | Increases (more resistance) |
| Smaller conductor (higher AWG number) | Increases (less circular-mil area) |
| Higher current | Increases (drop is proportional to current) |
| Copper instead of aluminum | Decreases (lower K, lower resistance) |
Checkpoint · Electrical Theory & Calculations
Question 1 of 7
An electric range element has a resistance of 12 ohms and carries 10 amperes. According to Ohm's law, what is the voltage applied across the element?
Module 2 · Services, Grounding & Bonding
Where the building connects to the utility — and how it’s made safe. This module covers services and service conductors (Article 230) and the most-confused topic on the exam, grounding and bonding (Article 250).
2.1 Services & Service Conductors
The is the conductors and equipment that bring power from the utility into the building. A one-family dwelling service must be rated at least 100 amperes, three-wire. run from the meter to the service disconnect and must have an ampacity at least equal to the calculated load.[1]
A special allowance helps here: for 120/240-volt single-phase dwelling services and main feeders, the NEC permits conductors sized at 83% of the service rating (the dwelling services/feeders table), so a 200-amp dwelling service can use 2/0 copper instead of the larger size the general ampacity table would demand.
| Item | Rule |
|---|---|
| Minimum dwelling service | 100 A, three-wire (one-family dwelling) |
| Service conductor ampacity | At least the calculated load |
| Dwelling 83% allowance | 120/240 V single-phase services/feeders may be sized at 83% |
| Number of disconnects | Service disconnect grouped; up to six in some editions |
| Working space | Keep 110.26 clearances at the service equipment |
2.2 Grounding & Bonding
The exam constantly tests the difference. connects the system to the (rod, pipe, plate, or concrete-encased “Ufer”) through the to stabilize voltage and dissipate surges. joins all metal together so it’s at the same potential, creating the low-impedance path that lets fault current trip the breaker.[2]
Grounding (to earth)
Connecting the system to the earth.
- Path: grounding electrode conductor (GEC) → electrode (rod, pipe, plate, Ufer)
- Sized by Table 250.66 (to a rod: never larger than 6 AWG copper)
- Stabilizes voltage; dissipates lightning and surges
Bonding (metal to metal)
Joining all metal so it’s at the same potential.
- Path: equipment grounding conductor (EGC) + bonding jumpers
- Sized by Table 250.122 (by breaker size)
- Creates the low-impedance fault path that trips the breaker
Two sizing tables anchor this topic. The is sized from Table 250.66 — but capped at 6 AWG copper to a rod and 4 AWG copper to a concrete-encased electrode, no matter how big the service is. The is sized from Table 250.122 by the breaker rating. At the service, the ties the bus to the equipment ground; on a , the does the same job.
| Conductor | Sized by | Key cap / note |
|---|---|---|
| Grounding electrode conductor (GEC) | Table 250.66 | ≤ 6 AWG Cu to a rod; ≤ 4 AWG Cu to a Ufer |
| Equipment grounding conductor (EGC) | Table 250.122 | By overcurrent-device rating (e.g., 60 A → 10 AWG Cu) |
| Main bonding jumper | Table 250.102 (like the GEC) | Bonds neutral to ground at the service |
| System bonding jumper | Table 250.102 | Same job for a separately derived system |
| Overcurrent device rating | Minimum copper EGC |
|---|---|
| 15 A | 14 AWG |
| 20 A | 12 AWG |
| 60 A | 10 AWG |
| 100 A | 8 AWG |
| 200 A | 6 AWG |
Checkpoint · Services, Grounding & Bonding
Question 1 of 9
Under the NEC, what is the minimum ampacity permitted for the ungrounded service-entrance conductors and disconnecting means supplying a one-family dwelling served by a 120/240-volt single-phase system?
Module 3 · Feeders & Load Calculations
How you turn a building’s loads into the right conductor and overcurrent sizes. This module covers load calculations (Article 220) and feeders (Article 215).
3.1 Load Calculations (Article 220)
For a dwelling, the general lighting and receptacle load is figured at 3 volt-amperes per square foot of habitable area. You add the two small-appliance circuits and the laundry circuit (1,500 VA each), then apply demand factors: the first 3,000 VA at 100%, 3,001–120,000 VA at 35%, and the remainder at 25%.[1]
Continuous loads (running 3 hours or more) are sized at 125%. Specific loads have their own demand tables — ranges (220.55), dryers (220.54), and others — that reflect the fact that not everything runs at full load at once.
| Portion of load | Demand factor |
|---|---|
| First 3,000 VA | 100% |
| 3,001 to 120,000 VA | 35% |
| Remainder over 120,000 VA | 25% |
3.2 Feeders (Article 215)
A runs between the service equipment and the final branch-circuit overcurrent device. Its conductors must have an ampacity (before adjustment) of at least the noncontinuous load plus 125% of the continuous load, and never less than the calculated load it carries.[1]
Fixed electric space heating is treated as a , so it gets the 125% factor. When a feeder supplies subpanels, its ampacity must cover the total calculated load of everything downstream.
| Situation | Sizing rule |
|---|---|
| Continuous + noncontinuous load | Noncontinuous + 125% of continuous (before adjustment) |
| Fixed electric space heating | Treated as a continuous load (125%) |
| Feeder to subpanels | Ampacity ≥ total calculated downstream load |
| After adjustment factors | Still ≥ the calculated load after temperature/fill corrections |
Checkpoint · Feeders & Load Calculations
Question 1 of 5
Under Article 215, feeder conductors that supply a combination of continuous and noncontinuous loads must have an allowable ampacity, before applying any adjustment or correction factors, of not less than what value?
Module 4 · Wiring Methods, Conductors & Fill
The biggest single area of the exam. This is the day-to-day of the trade: choosing a wiring method, sizing and protecting conductors, and getting conduit and box fill right.
4.1 Wiring Methods & Conductors
Know the common raceways and cables by their articles. (Article 358) is thin-wall steel tubing — supported within 3 feet of every box and every 10 feet, with no more than 360 degrees of bends between pull points, and not permitted where subject to severe physical damage.
(Article 334, “Romex”) is for dry locations and dwellings, secured within 12 inches of a box and every 4.5 feet. (Article 344) is the heavy-duty choice allowed almost anywhere.[1]
(Table 310.16) is the current a conductor can carry continuously — but the (240.4(D)) caps the breaker regardless: 14 AWG → 15 A, 12 AWG → 20 A, 10 AWG → 30 A. The runs with the circuit to provide the fault path, and Article 300 holds the general rules (securing, protection from damage) for all wiring methods.
| Method | Article | Key rules |
|---|---|---|
| EMT (electrical metallic tubing) | 358 | Support within 3 ft of boxes, every 10 ft; ≤360° bends; ream cut ends; not for severe damage |
| Type NM cable (Romex) | 334 | Dry locations/dwellings; secure within 12 in of box, every 4.5 ft |
| Rigid metal conduit (RMC) | 344 | Heavy-wall, threaded; permitted in nearly all locations |
| General wiring requirements | 300 | Securing, protection from physical damage, raceway rules |
| Conductor | Max overcurrent device |
|---|---|
| 14 AWG copper | 15 A |
| 12 AWG copper | 20 A |
| 10 AWG copper | 30 A |
4.2 Conduit & Box Fill
(Chapter 9, Table 1) limits how full a raceway can be: 53% for one conductor, 31% for exactly two, and 40% for three or more. The two- conductor case is the most restrictive on purpose — a tight pair can jam and damage insulation during the pull.[1]
Most room — a single wire
Most restrictive — eases jamming
The common real-world case
(314.16) makes sure a box is big enough. Each conductor counts as one; all grounding conductors together count as one; all cable clamps together count as one; and each device on a yoke counts as two— all based on the largest conductor involved. Multiply the total count by that conductor’s volume allowance.
Each current-carrying conductor
Each ungrounded and grounded (neutral) conductor passing through or terminating.
All equipment grounding conductors
All EGCs together count as ONE, based on the largest EGC present.
All internal cable clamps
All clamps together count as ONE, based on the largest conductor in the box.
Each support fitting (fixture stud / hickey)
Based on the largest conductor in the box.
Each device on a yoke/strap (switch, receptacle)
Each yoke counts as TWO, based on the largest conductor connected to it.
Volume allowance per conductor (Table 314.16(B))
Checkpoint · Wiring Methods, Conductors & Fill
Question 1 of 10
Electrical metallic tubing (EMT) is identified in the NEC under which article governing its use, installation, and construction as a wiring method?
Module 5 · Overcurrent, GFCI/AFCI & Safety
Protection and people. This module covers overcurrent protection (Article 240), GFCI/AFCI and receptacle placement (210.8, 210.12, 210.52), and electrical safety and working space.
5.1 Overcurrent Protection
An (fuse or breaker) exists to protect the conductor from overheating. It must be readily accessible — the operating handle no more than 6 ft 7 in above the floor (240.24) — and not located over steps or in bathrooms or clothes closets.[1]
Two big rules: the (240.4(D)) caps protection on small wires, and a is allowed under the 10-foot and 25-foot tap rules (240.21) to connect a smaller conductor to a larger circuit under specific conditions (the 25-ft tap must be at least one-third the feeder OCPD rating).
| Rule | Requirement |
|---|---|
| Purpose | Protect the conductor/equipment from excessive current |
| Readily accessible (240.24) | Handle ≤ 6 ft 7 in above floor; not over steps, in baths, or in closets |
| Small-conductor cap (240.4(D)) | 14 AWG → 15 A, 12 AWG → 20 A, 10 AWG → 30 A |
| 10-ft tap (240.21(B)(1)) | Tap ampacity ≥ the load and the device it supplies |
| 25-ft tap (240.21(B)(2)) | Tap ampacity ≥ one-third of the feeder OCPD rating |
5.2 GFCI, AFCI & Receptacles
Don’t mix these up. A (210.8) protects people from shock by sensing tiny leakage to ground (≈4–6 mA) — required in kitchens, bathrooms, garages, basements, laundry, and outdoors. An (210.12) protects against fire by detecting arcing faults — required in dwelling living areas like bedrooms.[4]
GFCI — protects PEOPLE
Senses current leaking to ground (≈4–6 mA) and trips to stop electric shock.
- Code: 210.8
- Where (water/earth): kitchens, baths, garages, basements, outdoors, laundry
- Hazard: shock / electrocution
AFCI — protects PROPERTY
Detects dangerous arcing faults and opens the circuit to prevent fire.
- Code: 210.12
- Where (living space): bedrooms, living rooms, most dwelling rooms
- Hazard: fire from arcing
Receptacle spacing (210.52) follows the 6-foot rule: no point along a wall line is more than 6 feet from a receptacle, so receptacles sit no more than 12 feet apart, and any wall 2 feet or wider gets one. In kitchens, countertop receptacles are placed so no point is more than 24 inches from one, and any counter 12 inches or wider needs a receptacle. Replacing a receptacle where GFCI is now required triggers GFCI protection.
| GFCI (210.8) | AFCI (210.12) | |
|---|---|---|
| Protects | People from electric shock | Property from fire |
| Senses | Current leakage to ground (≈4–6 mA) | Arcing-fault signature |
| Where | Kitchens, baths, garages, basements, outdoors, laundry | Dwelling living areas (bedrooms, living rooms) |
| Location | Rule |
|---|---|
| General wall spacing | No point > 6 ft from a receptacle (≤ 12 ft apart) |
| Which walls | Any wall space 2 ft or wider |
| Kitchen countertop spacing | No point > 24 in from a receptacle |
| Which counters | Any counter 12 in or wider |
5.3 Safety & Working Space
(110.26) keeps electricians safe at the panel: for systems up to 150 volts to ground, at least 3 feet deep (Condition 1), 30 inches wide (or the equipment width), and 6½ feet of headroom, with doors able to open at least 90 degrees. The space must stay clear — no storage.[1]
Beyond the Code, OSHA governs job-site safety. The core rule is to treat every conductor as energized until it’s tested dead, and to use (OSHA 1910.147): de-energize, lock, tag, and verify before servicing.[5] Wear the right PPE and respect minimum approach distances to energized parts.
| Dimension | Minimum |
|---|---|
| Depth (Condition 1, clear) | 3 ft (36 in) |
| Width | 30 in or the equipment width, whichever is greater |
| Headroom | 6½ ft (78 in) |
| Door swing | At least 90 degrees |
Checkpoint · Overcurrent, GFCI/AFCI & Safety
Question 1 of 10
What is the primary purpose of the overcurrent protective device that protects a branch-circuit conductor under Article 240?
How to Use This Journeyman Electrician Study Guide
This guide is built to be worked, not just read. The most efficient path to a pass:
- Master the calculations. Ohm’s law, power, voltage drop, conduit and box fill, and load calcs show up everywhere — drill them until they’re automatic.
- Learn to navigate the Code, not memorize it. The exam is open-book; speed at finding the right article and table is what wins.
- Check off as you go. Use the Study Guide Contents to mark each section done; it raises your exam-readiness score.
- Take every checkpoint. The end-of-module quizzes show you exactly which topics need another pass.
- Drill the weak area. Send it into the flashcards and a practice test until the score climbs.
- Confirm your Code edition. Study from the NEC edition your state has adopted (2023, 2020, or 2017) — article and table numbers can shift between editions.
Journeyman Electrician Concept Questions
Common electrical concepts candidates study for the journeyman exam — each answered briefly and backed by an official source (NFPA, OSHA, DOE, NIST). Test yourself, then drill them as flashcards.
Journeyman Electrician Glossary
The high-yield electrical and NEC terms in one place — hover any dotted term in the guide, or flip the whole deck here as a self-grading flashcard set.
- AFCI
- Arc-Fault Circuit Interrupter — detects dangerous arcing faults to prevent fire, required in dwelling living areas (210.12).
- Ampacity
- The maximum current a conductor can carry continuously without exceeding its temperature rating (Table 310.16).
- AWG
- American Wire Gauge — the sizing system for conductors; a smaller AWG number means a larger conductor.
- Bonding
- Joining metal parts together so they are at the same potential, creating the low-impedance fault path that trips the breaker.
- Box fill
- The required minimum box volume based on the conductors, clamps, fittings, and devices inside it (314.16).
- Branch circuit
- The conductors between the final overcurrent device and the outlets it serves (Article 210).
- Conductor
- A wire or other material that carries current; sized by AWG or kcmil and rated for an insulation temperature.
- Conduit fill
- The maximum percent of a raceway's cross-section conductors may occupy: 53% for one, 31% for two, 40% for three or more (Chapter 9, Table 1).
- Continuous load
- A load expected to operate for three hours or more; sized at 125% for conductors and overcurrent devices.
- Current
- The flow of electric charge, measured in amperes (I or A); the same in every part of a series circuit.
- EMT
- Electrical Metallic Tubing — a thin-wall steel raceway (Article 358); supported within 3 ft of boxes and every 10 ft.
- Equipment grounding conductor
- The conductor (EGC) that bonds non-current-carrying metal back to the source, providing the fault-current path; sized by Table 250.122.
- Feeder
- Conductors between the service equipment and the final branch-circuit overcurrent device (Article 215).
- GFCI
- Ground-Fault Circuit Interrupter — trips on small current leakage to ground (≈4–6 mA) to protect people from shock (210.8).
- Grounded conductor
- The conductor intentionally connected to ground, usually the neutral; not the same as the equipment grounding conductor.
- Grounding
- Connecting the electrical system to the earth through a grounding electrode conductor and electrode (Article 250).
- Grounding electrode
- The conducting object — ground rod, water pipe, concrete-encased (Ufer) electrode, or plate — that makes earth contact.
- Grounding electrode conductor
- The conductor (GEC) connecting the grounded system or equipment to the grounding electrode; sized by Table 250.66.
- Lockout/tagout
- The OSHA procedure (1910.147) for de-energizing, locking, tagging, and verifying equipment safe before servicing it.
- Main bonding jumper
- The connection at the service that bonds the grounded (neutral) conductor to the equipment ground and enclosure.
- NEC
- The National Electrical Code (NFPA 70) — the model code, updated every three years, that journeyman exams are based on.
- Ohm's law
- The rule that voltage equals current times resistance (E = I × R); rearranged, it gives current or resistance from the other two values.
- Overcurrent device
- A fuse or circuit breaker that opens the circuit when current would overheat the conductor (Article 240).
- Parallel circuit
- A circuit with multiple paths; voltage is the same across every branch and total resistance is less than the smallest branch.
- Power factor
- The ratio of real power (watts) to apparent power (volt-amperes) in an AC circuit; 1.0 (unity) means all the power does useful work.
- Raceway
- An enclosed channel — conduit or tubing — designed to hold conductors.
- Resistance
- Opposition to current flow, measured in ohms (Ω); resistances add in series and combine reciprocally in parallel.
- Rigid metal conduit
- RMC — heavy-wall threaded steel conduit (Article 344) permitted in nearly all locations, including severe physical damage.
- Separately derived system
- A system whose power is derived from a source (like a transformer or generator) with no direct electrical connection to the supply conductors.
- Series circuit
- A circuit with one current path; current is the same everywhere and resistances add up.
- Service
- The conductors and equipment that deliver electricity from the utility to a building's wiring (Article 230).
- Service-entrance conductors
- The conductors from the service point or meter to the service disconnect; a one-family dwelling service must be at least 100 A.
- Single-phase
- An AC supply with one alternating voltage (commonly 120/240 V in dwellings); power = E × I × power factor.
- Small-conductor rule
- 240.4(D): caps overcurrent protection at 15 A for 14 AWG, 20 A for 12 AWG, and 30 A for 10 AWG copper, regardless of ampacity.
- System bonding jumper
- The equivalent of the main bonding jumper for a separately derived system, such as a transformer secondary.
- Tap conductor
- A conductor with overcurrent protection ahead of it larger than its ampacity normally allows; permitted under the 10-ft and 25-ft tap rules (240.21).
- Three-phase
- An AC supply with three voltages 120° apart, used for larger loads; power = 1.732 × E × I × power factor.
- Type NM cable
- Nonmetallic-sheathed cable (Romex), used mainly in dry locations and dwellings (Article 334); secured within 12 in of boxes and every 4.5 ft.
- Voltage
- Electrical pressure or potential difference, measured in volts (E or V) — what pushes current through a circuit.
- Voltage drop
- The loss of voltage along a conductor due to its resistance; the NEC recommends ≤3% on a branch or feeder and ≤5% total.
- Working space
- The clear space required in front of equipment so it can be serviced safely (110.26) — for ≤150 V, at least 3 ft deep, 30 in wide, 6½ ft high.
Journeyman Electrician Study Guide FAQ
It varies by state, but a typical journeyman electrician exam has about 80 to 100 questions and a time limit of roughly 4 hours. Texas, for example, uses an 80-question PSI exam with a 4-hour limit. Most journeyman exams are open-book, so you may use the National Electrical Code during the test.
Most jurisdictions require about 70% correct to pass, though the exact cut score is set by each state or licensing board. Because the exam is largely code-based and open-book, knowing how to navigate the NEC quickly is as important as memorizing facts.
Exams are based on whichever edition of the National Electrical Code (NFPA 70) your jurisdiction has adopted. The current edition is the 2023 NEC, but states adopt on a lag — some are still on the 2020 or 2017 edition. Always confirm the adopted edition with your licensing board before testing.
Electrical theory (Ohm's law, power, series and parallel circuits), electrical calculations (load calcs, voltage drop, conduit and box fill, conductor sizing), and NEC code — wiring methods, grounding and bonding, overcurrent protection, services and feeders, motors, and safety. Calculations and code lookup carry the most weight.
In most states, yes — you can bring and use a tabbed copy of the adopted NEC edition. Because of that, exam success depends heavily on being able to find the right article and table quickly. Practice navigating the code, not just memorizing it.
Work through the five modules: theory and calculations first, then services and grounding, feeders and load calcs, wiring methods and fill, and overcurrent, GFCI/AFCI, and safety. Take each checkpoint, then drill gaps with our free practice test and flashcards before exam day.
Yes. This study guide, the checkpoint quizzes, the glossary, the practice test, and the flashcards are 100% free with no account required.
References
- 1.National Fire Protection Association. “NFPA 70, National Electrical Code (NEC).” nfpa.org. ↑
- 2.National Fire Protection Association. “Grounding vs. Bonding (NEC Article 250).” nfpa.org. ↑
- 3.Occupational Safety and Health Administration. “Electrical — Safety Standards.” osha.gov. ↑
- 4.Occupational Safety and Health Administration. “Ground-Fault Protection on Construction Sites (1926.404).” osha.gov. ↑
- 5.Occupational Safety and Health Administration. “The Control of Hazardous Energy (Lockout/Tagout), 1910.147.” osha.gov. ↑
- 6.Texas Department of Licensing and Regulation. “Electricians — Licensing & Examination.” tdlr.texas.gov. ↑
- 7.PSI Exams. “Electrical Examination Candidate Information.” psiexams.com. ↑
- 8.U.S. Department of Energy. “Determining Electric Motor Load and Efficiency.” energy.gov. ↑
- 101.National Institute of Standards and Technology. “The Ohm and Ohm's Law.” nist.gov, accessed 20 June 2026. ↑

Career Employer
Career Employer is the ultimate resource to help you get started working the job of your dreams. We cover topics from general career information, career searching, exam preparation with free study materials, career interviewing, and becoming successful in your career of choice.
All PostsCareer Employer’s Editorial Process
Here at Career Employer, we focus a lot on providing factually accurate information that is always up to date. We strive to provide correct information using strict editorial processes, article editing, and fact-checking for all of the information found on our website. We only utilize trustworthy and relevant resources. To find out more, make sure to read our full editorial process page here.
