This free EPA 608 study guide covers everything the EPA Section 608 Technician Certification exam tests, organized to the exam’s four official sections — Core plus Type I, Type II, and Type III.[1]
It’s interactive, not a wall of text: every module has built-in checkpoint quizzes, flashcards, and practice questions, so you learn by doing — not just reading.
Section 608 is part of the federal . Everyone takes the Core section, then the type section(s) for the equipment they service — or all three for . Read a module, test yourself at each checkpoint, then drill gaps with our free practice test and flashcards. This guide is a high-yield overview that maps the tested content — not a full HVAC textbook.
EPA 608 Exam Snapshot
| Detail | EPA 608 Exam |
|---|---|
| Sections | Core + Type I + Type II + Type III |
| Questions | 25 multiple-choice per section |
| Format | Multiple choice (Type I may be open-book; Core/II/III/Universal proctored, closed-book) |
| Passing score | ≈70% per section (about 18 of 25); each section passed independently |
| Universal | Earned by passing Core + Type I + II + III |
| Certifying body | EPA-approved certifying organizations (e.g., ESCO, Mainstream, HVAC Excellence) |
| Recertification | None — the certification never expires |
| Eligibility | Open to anyone; no experience prerequisite to test |
The exam is built in sections, and which ones you take depends on the equipment you work on. Everyone takes Core; technicians then add the type(s) they need.[1] Here is how the sections map to real-world equipment:
Each section has the same 25 questions and the same ~70% passing standard, but they are scored separately — you can pass one and fail another.[1]
Core
Required of everyone. Ozone science, regulations, recovery, safety, and recordkeeping — the foundation for every type.
Type I
Small appliances — factory-sealed units with 5 lb or less of refrigerant (refrigerators, window AC, vending machines).
Type II
High- and very high-pressure appliances — split systems, supermarket racks, heat pumps (R-22, R-410A, R-404A).
Type III
Low-pressure appliances — centrifugal (centrif) chillers that run under a vacuum (R-11, R-123, R-1233zd).
Universal
Not a separate exam — you earn it by passing Core plus Type I, II, and III. Covers all equipment.
Module 1 · Core
Required of everyone, and the foundation for every type. The Core section tests the “why” behind the rules — ozone and climate science, the refrigerant phase-out, the Clean Air Act regulations, and the basics of recovery and safety that apply no matter what equipment you service.
1.1 Ozone, Climate & the Phase-Out
The whole program exists to protect the in the , which absorbs harmful ultraviolet radiation. When a stable or refrigerant is released, it drifts up over years; UV light then frees a chlorine atom, and a single chlorine atom catalytically destroys thousands of ozone molecules.[7]
- 1
1. Refrigerant is released
A stable CFC or HCFC molecule is vented or leaks at ground level and does not break down.
- 2
2. It drifts to the stratosphere
Because it is so stable, the molecule rises over years until UV light reaches it.
- 3
3. UV frees a chlorine atom
Ultraviolet light splits the molecule, releasing a reactive chlorine (Cl) atom.
- 4
4. Chlorine destroys ozone
One chlorine atom catalytically destroys thousands of ozone (O₃) molecules before it is removed.
Two numbers describe a refrigerant’s impact: (ODP, relative to CFC-11) and (GWP, relative to carbon dioxide). A refrigerant can have zero ODP yet a high GWP — that is exactly the case for the refrigerants now in wide use.[8]
CFC (e.g., R-12)
High ODP, high GWP. Chlorine-bearing. Production banned (1996).
HCFC (e.g., R-22)
Low ODP, high GWP. Transitional. Production/import ended Jan 1, 2020.
HFC (e.g., R-410A, R-134a)
Zero ODP, high GWP. Being phased DOWN under the AIM Act.
HFO (e.g., R-1234yf, R-1233zd)
Zero ODP, very low GWP. The low-impact replacements (often A2L, mildly flammable).
The (1987) set the phase-out schedule: CFCs first (U.S. production ended in 1996), then HCFCs (R-22 production and import ended January 1, 2020). Now the is phasing down high-GWP HFCs for their climate impact, steering the industry toward low-GWP refrigerants.[6]
| Class | Examples | Ozone / climate | Status |
|---|---|---|---|
| CFC | R-12, R-11 | High ODP, high GWP | Banned (U.S. production ended 1996) |
| HCFC | R-22, R-123 | Low ODP, high GWP | Phased out (R-22 ended Jan 1, 2020) |
| HFC | R-410A, R-134a, R-404A | Zero ODP, high GWP | Being phased down (AIM Act) |
| HFO | R-1234yf, R-1233zd | Zero ODP, very low GWP | The low-impact replacements |
1.2 Regulations, Recovery & Safety
The single most important rule in Section 608: since 1995 it is illegal to knowingly refrigerant during service, maintenance, repair, or disposal. Only small, unavoidable during good-faith recovery are allowed, and the prohibition now extends to most HFC substitutes too.[2]
Three terms are constantly confused — and constantly tested. To is just to remove refrigerant into a container. To is to clean it on-site for reuse in the same owner’s equipment. To is to reprocess it to like-new purity meeting the standard and verify it — the only refrigerant that may be sold to a new owner.[4]
Recover
Remove refrigerant from an appliance and store it in an external container — no cleaning or testing.
Recycle
Clean the refrigerant on-site with oil separation and filter-driers for re-use in the SAME owner's equipment — not laboratory-tested to a purity standard.
Reclaim
Reprocess refrigerant to like-new purity meeting the AHRI 700 standard and chemically verify it. Only reclaimed refrigerant may be resold to a new owner.
Buying refrigerant is restricted: under the sales restriction, regulated refrigerants may be sold only to certified technicians, and the restriction now covers most HFCs.[9] Store recovered refrigerant in a DOT-approved (gray body, yellow top) and never fill it past 80% by weight, because liquid refrigerant expands as it warms.
Recovery cylinder
Gray body with a YELLOW top (shoulder). Used to store recovered refrigerant; never fill past 80% by weight.
DOT requirement
Must be a DOT-approved (or UL-listed) cylinder, hydrostatically tested every 5 years, with a working overfill-protection device.
Disposable (one-time) cylinders
Hold virgin refrigerant only. It is illegal to refill them, and they must be evacuated to a deep vacuum before recycling the metal.
| Hazard | Why it's dangerous | Protection |
|---|---|---|
| Asphyxiation | Refrigerant vapor displaces oxygen in a confined space | Ventilate; use an oxygen-deprivation monitor |
| Frostbite | Liquid refrigerant is extremely cold and can freeze skin/eyes | Wear gloves and eye protection |
| Phosgene / toxic gas | Refrigerant exposed to an open flame can form toxic gases | No open flames; never expose refrigerant to fire |
| Over-pressure | Overfilled cylinders can rupture as liquid expands | Fill to ≤ 80%; use an overfill-protection device |
Checkpoint · Core
Question 1 of 10
At what altitude does the ozone layer that Section 608 regulations aim to protect primarily reside?
Module 2 · Type I — Small Appliances
The most accessible certification — and the only one that may be taken at home. Type I covers : the factory-sealed units that hold a small charge, like household refrigerators and window air conditioners.
2.1 What Counts as a Small Appliance
The definition is exact: a small appliance is fully manufactured, charged, and at the factory with 5 pounds or less of refrigerant. Refrigerators, freezers, window AC units, packaged terminal units, dehumidifiers, water coolers, and vending machines all qualify.[1]
The make-or-break test is the factory seal. A unit that was field-assembled and field-charged on site — like a split-system central AC — is never a small appliance, even if it holds less than 5 pounds.
| Equipment | Small appliance? | Why |
|---|---|---|
| Household refrigerator | Yes | Factory-sealed, ≤ 5 lb |
| Window air conditioner | Yes | Factory-sealed, ≤ 5 lb |
| Vending machine / water cooler | Yes | Factory-sealed, ≤ 5 lb |
| Split-system central AC | No | Field-assembled and field-charged |
| Supermarket refrigeration rack | No | Large, field-charged high-pressure system |
2.2 Type I Recovery Requirements
With recovery equipment made after November 15, 1993, a technician must recover at least 90% of the charge when the compressor is operating, and at least 80% when the compressor is not operating. A running compressor helps push refrigerant out, so more can be recovered.[3]
Small appliances are the only equipment where (passive recovery, using the appliance’s own compressor or pressure) is allowed. Larger equipment must use gear with its own compressor.
| Condition | Minimum recovered | Equipment |
|---|---|---|
| Compressor operating | 90% of the charge | Passive or active, post-Nov 15 1993 |
| Compressor not operating | 80% of the charge | Passive or active, post-Nov 15 1993 |
| Larger (non-small) equipment | Per Type II/III rules | Self-contained (active) only |
Checkpoint · Type I — Small Appliances
Question 1 of 10
Under Section 608, a 'small appliance' is defined as a product that is fully manufactured, charged, and hermetically sealed in a factory and contains how much refrigerant?
Module 3 · Type II — High-Pressure
The bread-and-butter of HVAC. Type II covers — split-system AC, heat pumps, and supermarket refrigeration racks — and is the certification most field technicians need.
3.1 High-Pressure Refrigerants & Equipment
High-pressure refrigerants operate above atmospheric pressure at normal temperatures. The classic ones are R-22 (the legacy HCFC), R-410A (the high-pressure HFC that replaced it), and R-404A and R-407C in commercial refrigeration.[1]
R-410A operates at much higher pressures than R-22, so gauges, hoses, and recovery equipment must be rated for it — you cannot safely service an R-410A system with R-22-rated tools. Pressure and temperature move together (the pressure-temperature relationship), which is how a technician uses a P/T chart to check charge and superheat.
| Refrigerant | Class | Where you see it |
|---|---|---|
| R-22 | HCFC (high-pressure) | Legacy residential/commercial AC (phased out) |
| R-410A | HFC (very high-pressure) | Modern residential/commercial AC and heat pumps |
| R-404A | HFC (high-pressure) | Commercial/supermarket refrigeration |
| R-407C | HFC (high-pressure) | R-22 retrofit replacement |
3.2 Recovery Vacuum & Leak Repair
Type II recovery levels are set in and depend on the charge size. With post-November-15-1993 equipment, a system with a charge 200 lb or less is recovered to 0 in. Hg (atmospheric), and a charge over 200 lb to 10 in. Hg vacuum.[3]
Small appliance (Type I), compressor running
Recover ≥ 90% of charge
Small appliance (Type I), compressor not running
Recover ≥ 80% of charge
High-pressure (Type II), charge ≤ 200 lb
0 in. Hg vacuum (atmospheric)
High-pressure (Type II), charge > 200 lb
10 in. Hg vacuum
Low-pressure (Type III)
25 mm Hg absolute
For appliances containing 50 pounds or more, owners must repair leaks when the annual exceeds the threshold: 10% for comfort cooling, 20% for commercial refrigeration, and 30% for industrial process refrigeration. Repairs generally must be completed within 30 days and then verified.[5] When dehydrating a system to remove moisture, technicians pull a deep vacuum of about 500 measured with a micron gauge.
| Appliance category | Annual leak-rate trigger |
|---|---|
| Comfort cooling (e.g., building AC) | 10% per year |
| Commercial refrigeration | 20% per year |
| Industrial process refrigeration | 30% per year |
Checkpoint · Type II — High-Pressure
Question 1 of 10
Type II certification covers technicians who service high- and very high-pressure appliances. Which of the following refrigerants is a high-pressure refrigerant covered under Type II?
Module 4 · Type III — Low-Pressure
The specialty section. Type III covers — the big centrifugal chillers that run under a vacuum. They behave differently from everything else, which is why they get their own rules.
4.1 Low-Pressure Chillers & Vacuum
A low-pressure appliance uses a refrigerant that boils below atmospheric pressure, so the low side of the system runs under a vacuum at normal temperatures. The classic refrigerants are R-11 (the original) and R-123 (its HCFC replacement), with R-1233zd as a near-zero-GWP HFO option.[1]
Because the low side is under a vacuum, the leak problem is reversed: air and moisture leak into the system rather than refrigerant leaking out. Type III recovery uses its own unit — 25 with post-1993 equipment — a value measured from a perfect vacuum, not the same as Type II’s inches of mercury vacuum.[3]
| Item | Detail |
|---|---|
| Refrigerants | R-11, R-123 (HCFCs); R-1233zd (HFO replacement) |
| Equipment | Centrifugal (centrif) chillers in large buildings |
| Operating pressure | Low side runs below atmospheric (under a vacuum) |
| Recovery level | 25 mm Hg absolute (post-Nov 15 1993 equipment) |
| Leak direction | Air and moisture leak IN, not out |
4.2 Purge Units & Safe Service
Air and other that leak into a low-pressure chiller raise condensing pressure and cut efficiency, so a removes them while keeping the refrigerant. A purge unit running far more than usual signals an air leak that should be found and fixed. High-efficiency purge units are preferred because they release far less refrigerant per unit of air purged.[1]
Low-pressure vessels are protected from over-pressure by a set around 15 psig. That is why leak-testing is done with dry nitrogen kept below the disc setting — never oxygen (which can form a combustible mixture with the system’s oil) and never above ~15 psig (which would burst the disc).
| Topic | Rule | Why |
|---|---|---|
| Purge unit | Remove air/noncondensables; high-efficiency type preferred | Keeps efficiency up, minimizes refrigerant loss |
| Leak testing | Use dry nitrogen, kept below ~15 psig | Oxygen + oil can combust; over-pressure bursts the disc |
| Rupture disc | Relieves pressure around 15 psig | Protects the low-pressure vessel from rupture |
| R-123 handling | Ventilate; monitor exposure | R-123 is more toxic than R-11 |
Checkpoint · Type III — Low-Pressure
Question 1 of 10
Type III certification covers low-pressure appliances. What is the defining characteristic of a low-pressure refrigerant used in these systems?
Module 5 · Universal & Exam Strategy
The last module ties the sections together: how works, and the specific numbers that separate a pass from a fail.
5.1 Earning Universal Certification
Universal is not a separate exam. You earn it by passing Core plus all three type sections — Type I, II, and III. Each of the four sections is 25 questions and is scored independently at about a 70% pass standard, so you can pass some and retake others.[1]
Most field technicians pursue Universal because it covers every equipment type, but you only legally need the type(s) matching the equipment you service. Core is mandatory for all of them. Certification is delivered by EPA-approved organizations and, once earned, never expires.
| You service… | Certification needed |
|---|---|
| Refrigerators, window AC, vending machines | Core + Type I |
| Split AC, heat pumps, supermarket racks | Core + Type II |
| Centrifugal (low-pressure) chillers | Core + Type III |
| All of the above | Universal (Core + Type I + II + III) |
5.2 Numbers to Memorize
EPA 608 rewards memorizing a short list of exact figures. Lock these in and you’ll recognize most of the numeric questions instantly:
| Number | What it means |
|---|---|
| 5 lb or less | Defines a small appliance (Type I) |
| 90% / 80% | Type I recovery: compressor running / not running |
| Nov 15, 1993 | Cutoff for higher recovery-equipment standards |
| 50 lb | Charge at/above which leak-repair rules apply |
| 10% / 20% / 30% | Leak-repair triggers: comfort / commercial / industrial |
| 0 in. Hg / 10 in. Hg | Type II recovery: ≤ 200 lb / > 200 lb |
| 25 mm Hg absolute | Type III (low-pressure) recovery level |
| ~15 psig | Low-pressure chiller rupture-disc setting |
| 80% fill | Maximum fill of a recovery cylinder by weight |
| 1987 / 2020 | Montreal Protocol signed / R-22 production ended |
Checkpoint · Universal & Exam Strategy
Question 1 of 10
Which pair of properties does a technician compare when judging both the ozone and the climate effects of a refrigerant?
How to Use This EPA 608 Study Guide
This guide is built to be worked, not just read. The most efficient path to a pass:
- Master Core first. It’s required of everyone and underpins all three types — ozone science, the three R’s, and the venting rule.
- Study only the types you need. Type I for small appliances, Type II for high-pressure, Type III for chillers — or all three for Universal.
- Memorize the numbers. Use the “numbers to memorize” table — the exam leans hard on exact recovery levels and thresholds.
- Check off as you go. Use the Study Guide Contents to mark each section done; it raises your exam-readiness score.
- Take every checkpoint, then drill. Send weak sections into the flashcards and a practice test until each section’s score clears 70%.
EPA 608 Concept Questions
Common refrigerant-handling concepts candidates study for the EPA Section 608 exam — each answered briefly and backed by an official EPA source. Test yourself, then drill them as flashcards.
EPA 608 Glossary
The high-yield Section 608 terms in one place — hover any dotted term in the guide, or flip the whole deck here as a self-grading flashcard set.
- AHRI 700
- The industry purity standard that reclaimed refrigerant must meet before it can be sold to a different owner.
- AIM Act
- The American Innovation and Manufacturing Act of 2020, which directs the EPA to phase down high-GWP HFC refrigerants.
- CFC
- Chlorofluorocarbon — an early refrigerant (e.g., R-12) with high ozone depletion potential; U.S. production ended in 1996.
- Clean Air Act
- The federal law that gives the EPA authority to regulate air pollution, including the ozone-protection rules in Section 608.
- De minimis release
- A small, unavoidable release of refrigerant during good-faith recovery, which is not treated as illegal venting.
- Global warming potential
- GWP — a measure of how much heat a gas traps over time, relative to carbon dioxide (set at 1.0).
- HCFC
- Hydrochlorofluorocarbon — a transitional refrigerant (e.g., R-22) with lower ODP than CFCs; production/import ended Jan 1, 2020.
- Hermetically sealed
- Factory-sealed so the refrigerant circuit is closed; a key part of the small-appliance definition.
- HFC
- Hydrofluorocarbon — a chlorine-free refrigerant (e.g., R-410A, R-134a) with zero ODP but high GWP, now being phased down.
- HFO
- Hydrofluoroolefin — a newer refrigerant (e.g., R-1234yf, R-1233zd) with zero ODP and very low GWP; often mildly flammable (A2L).
- High-pressure appliance
- Type II equipment using a refrigerant that operates above atmospheric pressure (e.g., R-22, R-410A, R-404A).
- Inches of mercury (in. Hg)
- A vacuum unit used for high-pressure (Type II) recovery levels; e.g., 10 in. Hg for charges over 200 lb.
- Leak rate
- The percentage of an appliance's full charge lost per year; repair is required above set thresholds on appliances with 50+ lb.
- Low-pressure appliance
- Type III equipment using a refrigerant that boils below atmospheric pressure, so the low side runs under a vacuum (e.g., R-11, R-123).
- Microns
- A fine vacuum unit (1 micron = 0.001 mm Hg) used when dehydrating a system; about 500 microns is a typical deep-vacuum target.
- mm Hg absolute
- A pressure measured from a perfect vacuum; low-pressure (Type III) recovery must reach 25 mm Hg absolute.
- Montreal Protocol
- The 1987 international treaty that set the schedule for phasing out ozone-depleting substances.
- Noncondensables
- Gases such as air and nitrogen that do not condense in the system; they raise condensing pressure and lower efficiency.
- Ozone depletion potential
- ODP — a measure of how much a substance harms stratospheric ozone, relative to CFC-11 (set at 1.0).
- Ozone layer
- A region of the stratosphere rich in ozone that absorbs most of the sun's harmful ultraviolet radiation.
- Purge unit
- A device on a low-pressure chiller that removes air and noncondensables while retaining the refrigerant.
- Reclaim
- To reprocess refrigerant to like-new purity meeting the AHRI 700 standard and verify it chemically; the only refrigerant that may be resold to a new owner.
- Reclaimer
- An EPA-certified facility that reprocesses used refrigerant to AHRI 700 purity for resale.
- Recover
- To remove refrigerant from an appliance and store it in an external container, without cleaning or testing it.
- Recovery cylinder
- A reusable DOT-approved container (gray body, yellow top) for storing recovered refrigerant; never fill past 80% by weight.
- Recycle
- To clean recovered refrigerant on-site (oil separation, filter-driers) for reuse in the same owner's equipment.
- Rupture disc
- A pressure-relief device on a low-pressure chiller (set around 15 psig) that protects the vessel from over-pressure.
- Section 608
- The part of the U.S. Clean Air Act that regulates the handling of refrigerants in stationary air-conditioning and refrigeration equipment, including technician certification.
- Self-contained recovery
- Active recovery equipment with its own compressor that can pull refrigerant from an appliance on its own.
- Small appliance
- A product fully manufactured, charged, and hermetically sealed at the factory with 5 lb or less of refrigerant.
- Stratosphere
- The atmospheric layer above the troposphere (roughly 10–50 km up) where the protective ozone layer resides.
- System-dependent recovery
- Passive recovery that uses the appliance's own compressor or pressure to push refrigerant out; allowed only on small appliances.
- Universal certification
- The credential earned by passing Core plus Type I, II, and III; it covers all equipment types.
- Venting
- Knowingly releasing refrigerant to the atmosphere; prohibited under Section 608 during service, repair, or disposal since 1995.
EPA 608 Study Guide FAQ
The EPA 608 exam has four sections — Core plus Type I, Type II, and Type III — and each section has 25 multiple-choice questions. Everyone must take Core. You then take one or more type sections depending on the equipment you service, or all of them for Universal certification.
You must pass each section independently, and most EPA-approved certifying organizations require about 70% — roughly 18 of the 25 questions — on Core and on each type section. Passing Core plus all three type sections earns Universal certification.
Core covers ozone science, regulations, recovery, and safety and is required of everyone. Type I covers small appliances (5 lb or less), Type II covers high-pressure appliances, and Type III covers low-pressure chillers. Universal is earned by passing Core plus all three types — it is not a separate exam.
No — Section 608 technician certification is a one-time, lifetime credential that never expires. Anyone who maintains, services, repairs, or disposes of stationary air-conditioning or refrigeration equipment that could release refrigerant, or who buys regulated refrigerant, must be certified.
Start with the Core module — it is required of everyone and underpins all three types. Then study the type section(s) you need (or all three for Universal). Take each module checkpoint, memorize the recovery numbers, then drill gaps with our free practice test and flashcards before exam day.
Type I (small appliances) may be taken open-book and proctored by mail through some EPA-approved organizations. Core, Type II, Type III, and Universal must generally be taken closed-book at a proctored testing site. Confirm the format with your certifying organization.
Yes. This study guide, the checkpoint quizzes, the glossary, the practice test, and the flashcards are 100% free with no account required.
References
- 1.U.S. Environmental Protection Agency. “Section 608 Technician Certification Requirements.” epa.gov. ↑
- 2.U.S. Environmental Protection Agency. “Prohibitions Under Section 608.” epa.gov. ↑
- 3.U.S. Environmental Protection Agency. “Refrigerant Recovery and Recycling Equipment Requirements.” epa.gov. ↑
- 4.U.S. Environmental Protection Agency. “Stationary Refrigerant Reclamation.” epa.gov. ↑
- 5.U.S. Environmental Protection Agency. “Refrigerant Leaks.” epa.gov. ↑
- 6.U.S. Environmental Protection Agency. “Phaseout of Ozone-Depleting Substances.” epa.gov. ↑
- 7.U.S. Environmental Protection Agency. “Basic Ozone Layer Science.” epa.gov. ↑
- 8.U.S. Environmental Protection Agency. “Reduction of HFCs Under the AIM Act.” epa.gov. ↑
- 9.U.S. Environmental Protection Agency. “Sales Restriction on Refrigerants.” epa.gov. ↑

Career Employer
Career Employer is the ultimate resource to help you get started working the job of your dreams. We cover topics from general career information, career searching, exam preparation with free study materials, career interviewing, and becoming successful in your career of choice.
All PostsCareer Employer’s Editorial Process
Here at Career Employer, we focus a lot on providing factually accurate information that is always up to date. We strive to provide correct information using strict editorial processes, article editing, and fact-checking for all of the information found on our website. We only utilize trustworthy and relevant resources. To find out more, make sure to read our full editorial process page here.